Alpha 2000
F O R E M O S T I N A I R F I LT R AT I O N
High Capacity HEPA Filters
Bulletin PB1402-0107
ed at conventional 250 fpm velocities during the life
of the filters. The Alpha 2000 99.97% and 99.99%
high capacity 24” X 24” X 11.5” filter has a clean
pressure drop of 1.0 inch w.g. at 1500 cfm, com-
pared to standard Alpha Cell filters with a clean
pressure drop of 1.50 inch w.g. at the same air flow.
High Capacity Design
The Alpha 2000 High Capacity HEPA filter is avail-
able in a nominal 12” depth configuration. It is
designed for optimum performance and low operat-
ing costs in both new and replacement systems.
The Alpha 2000 saves space, energy, and material
and labor costs with 40% more media area than the
standard capacity Alpha Cell filter.
Save Replacement Material and Labor
Costs
Savings are significant with high capacity Alpha
2000 filters. They operate at lower velocities and
provide life cycles up to three times the life of stan-
dard capacity filters. Savings are achieved in
replacement materials and labor costs as a result of
fewer filters.
Save Space
Alpha 2000 HEPA filters operate at 500 fpm (2000
cfm for a 24” x 24” size) at 1.35 inch w.g. clean
pressure drop versus conventional Alpha Cell filters
that operate at 250 fpm and .80 inch w.g. clean
pressure drop.
Alpha 2000 Pressure Drop vs. Air Velocity
Construction
2.20
2.00
1.80
A popular construction option consists of 16 ga.
galvaneal frames and moisture-resistant microfine
wet-laid fiberglass media folded over hemmed-
edge low amplitude corrugated aluminum separa-
tors. The filter pack is bonded to the frame by a fire-
retardant urethane elastomer to provide a rigid
leak-free assembly.
HEPA
1.60
ULPA
1.40
1.20
1.00
0.80
0.60
0.40
0.20
0.00
Save Energy
Alpha 2000 filters in a conventional HEPA filter
0
125
250
375
500
625
Air Velocity (fpm)
bank impose a lighter load on the fan when operat-
Important Features
• Efficiencies are 99.97% and 99.99% on 0.30
and 99.9995% on 0.12 micrometer particles.
• High capacity Alpha 2000 filters can reduce the
filter bank size
• Corrugated aluminum separators stabilize the
moisture-resistant media pack (separator
style)
• Available as a separatorless media filter with a
self-supporting media pack (*Pureform)
• Available in a variety of frame materials in
gasket or fluid seal design.
Flanders Filters - Foremost in Air Filtration
Toll Free: 1-800-637-2803
1
Frame Materials: Alpha 2000 Filters are available in a variety of wood and metal frame materials such as parti-
cle board, plywood, galvanized steel and stainless steel.
Gasket and Fluid Seal: The standard gasket seal is 0.75” x 0.25” neoprene for installation on either the
upstream, downstream or both sides of the filter. The standard Fluid Seal is Flanders Blu-Jel® Seal which is a
two - part silicone material suitable for temperatures up to 390°F.
Faceguards (Optional): Faceguards are used to protect the filter media from mechanical damage. The typical
faceguard material is expanded aluminized steel. Galvanized 4 x 4 mesh welded wire and Type 304 stain-
less steel are also available.
Underwriters Laboratories Qualification: Alpha 2000 Filters are either UL900 Class 1 or Class 2 listed depending
on materials of construction.
UL 900 Class 1 — Flanders HEPA Filters are UL 900 Class 1 rated except those filters manufactured with non-
fire-retardant wood frames. Upon request, the filter will have a stamp indicating compliance with UL 900 Class
1.
UL 586 — UL 586 is typically required for Nuclear Grade HEPA Filters. Many of the Flanders non-Nuclear HEPA
Filters meet the requirements of UL 586. To be listed under UL 586, filters must be submitted to Underwriters
Laboratories for extensive testing including spot flame and environmental exposure to heated air. Upon request,
a numbered UL 586 label certifying that the filter meets Standard 586 can be applied to the filter (maximum size
is 24” x 30”).
Banks: Alpha Frames are designed for Alpha 2000 filters in built-up filter banks. Each filter is secured in the
frame with four bolt-type fasteners that either compress the gasket or press the knife edge into the gel in the fil-
ter channel to maintain a leak-tight seal.
Surelock HEPA Filter Housings are recommended for side-access applications. The filters are sealed in place
with either spring-loaded swing arm assemblies or a locking mechanism. The swing arm assemblies or locking
mechanism either compress the gasket or press the knife edge into the gel in the filter channel to maintain a
leak-tight seal.
3
Alpha 2000 HEPA Filter Dimensions and Capacities
Filter Depth
(inches)
Filter Size and Frame Actual Face Size
CFM Capacity at Clean
Pressure Drop, Inches w.g.
Weight
(lbs)
Depth Designator
(Inches
.95
1.35
1.75
11-1/2
GG-F
GC-F
24x24
24x12
1500
650
2000
920
2500
1180
38
26
YY-F
YUF
23-3/8x23-3/8
23-3/8x11-3/8
1350
610
1900
865
2450
1150
37
25
GN-F
24x30
12x12
1750
290
2550
430
3250
550
45
14
CC-F`
NOTE: The pressure drop for fluid seal (Separator or Pureform) and scan tested Pureform
filters will be approximately 15% higher.
Guide Specifications
1.0 General
2.3 (A 40-durometer closed-cell neoprene gasket)
(Silicone jel in a channel) shall be provided on
1.1 Alpha 2000 HEPA filters shall be extended media
(separator type) (Pureform separatorless type)
filters as manufactured by Flanders.
one or more sides to seal the filter in the mount-
ing device.
1.2 Filter sizes, capacities and construction options
shall be as scheduled on the drawings.
3.0 Performance
3.1 Initial and final resistances shall not exceed the
scheduled values.
1.3 Filters shall be (UL 900 Class 1)(UL586 listed.
3.2 Alpha 2000 HEPA Filters shall have a minimum
efficiency of 99.97% on 0.30 micrometer parti-
cles when tested at rated capacity on a Q-107
Penetrometer in accordance with IEST-RP-CC-
001.3, Type A. Measure the upstream and down
stream concentration of these particles with a
light scattering photometer, determine the pene-
tration and calculate the efficiency.
2.0 Filter Construction
2.1 The filter pack shall be constructed by pleating a
continuous sheet of non-woven water-resistant
fiberglass media around hemmed-edge corru-
gated aluminum separators. (or) The filter pack
shall be constructed by pleating a continuous
sheet of formed, corrugated medium so that the
pack is self-supporting without the use of spac-
ers of any kind, including separators, tape
strings, adhesives or strips of media.
3.3 Alpha 2000 Scan Tested HEPA Filters shall have
a minimum efficiency of 99.99% on 0.30 microm-
eter particles in accordance with IEST-RP-CC-
001.3, Type C. The scan test shall consist of
challenging the filter with a high concentration of
an approved oil aerosol or PSL Spheres.
Utilizing a photometer or particle counter, the
media pack and the pack- to- frame seal shall be
scanned to insure that there are no leaks greater
than .01% of the upstream concentration at 100
fpm face velocity
2.2 The filter pack shall be sealed into a (galvaneal)
409 stainless steel) (304 stainless steel) (parti-
cle board) (fire-retardant particleboard) (fire-
retardant plywood) frame with
a
fire
retardant(polyurethane foam) ( solid urethane)
sealant. (Steel frames shall be 16 ga.)(Wood
frames shall be 3/4” thick.)
®
REPRESENTED BY:
Flanders Filters, Inc.
531 Flanders Filter Road
Washington, NC 27889
Phone: (252) 946-8081
Toll Free: (800) 637-2803
Fax: (252) 946-3425
|
Lexmark 4800 User Manual
Philips Nb Scb2050 User Manual
Philips R6b2a260 User Manual
Samsung As09cm2n User Manual
Toshiba Printer 281c User Manual
Toshiba Ram Sm560ut E User Manual
Trane Air Conditioner 4ttx5024a1 User Manual
Whynter Arc 12h User Manual
Xerox Workcentre 7675 User Manual
Xpelair 91175aa User Manual